Schneider Electric ComPacT NS (MicroLogic P/H)
Solar inverter by Schneider Electric. Compatibility with energy supplier apps, Home Assistant and evcc.
At a glance
| Device type | Solar inverter [evcc template, 2026-10-19] |
|---|---|
| evcc support | Yes |
| Connection | Modbus RTU (RS485)Modbus TCP (inferred from evcc template parameters) [evcc template, 2026-10-19] |
| Local control (no cloud) | Yes via evcc's connection type [evcc template, 2026-10-19] |
| Home Assistant | Unknown know this? tell us (brand not yet checked) |
| Known firmware notes | Unknown know this? tell us |
Energy supplier apps
Supplier lists are published per brand (sometimes with model conditions). A brand match does not guarantee your exact model works — check the linked page or the supplier's app.
| Supplier / service | Status for Schneider Electric inverter | Source |
|---|---|---|
| Frank Energie | Not listed Schneider Electric is not on Frank Energie's inverter list | [source, 2026-10-19] |
| Tibber | Not listed Schneider Electric is not on Tibber's inverter list | [source, 2026-10-19] |
| Zonneplan | Not listed Zonneplan only lists its own hardware | [source, 2026-10-19] |
| Eneco | Unknown know this? tell us | — |
| ANWB Energie | Unknown know this? tell us | — |
| Vattenfall | Unknown know this? tell us | — |
Home Assistant integrations for Schneider Electric
Unknown know this? tell us — we have not yet checked Home Assistant support for Schneider Electric.
evcc details
| Template | schneider-micrologic (meter; usages: grid, pv, charge) [source, 2026-10-19] |
|---|---|
| Connection | Modbus RTU (RS485)Modbus TCP (inferred) |
| Capabilities | Unknown know this? tell us |
| Requirements | The trip unit has to be reachable over Modbus through a communication module: IFM (Modbus RTU) or IFE (Modbus TCP), or EIFE on MasterPacT MTZ. IFE and EIFE always use Modbus ID 255, the IFM uses the address set on its rotary switches.
4-pole versions measure the neutral directly. 3-pole versions need an external neutral voltage tap (ENVT) for this, connected and declared in the trip unit (system type 40 or 41). Without ENVT, power values are wrong whenever current flows in the neutral.
The power flow sign has to be set with "EcoStruxure Power Commission" so that the normal direction of flow counts as positive. Factory setting: from the top terminals to the bottom ones. [source, 2026-10-19] |
| Known caveats | None listed in the evcc template. |